Certification Record | |
| CUSTOMER | CLASS | FILE |
| FERRAZ SHAWMUT Inc. | 1422-30 | 012636_0_000 |
| 374 Merrimac St, | FUSES-Supplemental Fuses - Component Acceptance | |
| Newburyport | ||
| MA | ||
| 01950-1998 | ||
| USA | Refer to Class Description for program details | |
(Replaces: November 26, 2009)
Semiconductor Fuses:
Model "PSC" Square Body (sizes 30 to 33) Type Semi-Conductor Fuses:
Cat No A070URD232 or 2X32 (alternate cat.
no. A070UD232 or 2X32), followed by suffixes, 800 to 2000A, 700V ac, IR 700V
ac -200kA; This range may also have alternate
cat. No. A030ARGE 232 or 2X32 followed by suffixes.
Cat No A070URD33(alternate
cat. no. A070UD33), followed by suffixes, 300 to 1400A, 700Vac, IR
700Vac-200kA; note: >1100A to 1400A have reinforced terminals.
Cat No A065URD33(alternate
cat. no. A065UD33), followed by suffixes, 1401 to 1800A, 650Vac, IR
650Vac-200kA; note these ratings all have reinforced terminals
Cat No A060URD33(alternate
cat. no. A060UD33), followed by suffixes, 1801 to 2000A, 600Vac, IR
600Vac-200kA; note these ratings all have reinforced terminals
Cat No A055URD33(alternate
cat. no. A055UD33), followed by suffixes,2001 to 2250A, 500Vac, IR
500Vac-200kA; note these ratings all have reinforced terminals
Cat No A050URD33(alternate
cat. no. A050UD33), followed by suffixes,2251 to 2500A, 500Vac, IR
500Vac-200kA; note these ratings all have reinforced terminals
Cat No A070URD233 or 2X33 (alternate cat.
no. A070UD233 or 2X33), followed by suffixes, 1000 to 2800A, 700V ac, IR
700V ac -200kA; note: ratings 2201 to 2800A have reinforced terminals.
Cat No A065URD233 or 2X33 (alternate cat.
no. A065UD233 or 2X33), followed by suffixes, 3000 to 3600A, 650V ac, IR
650V ac -200kA; note these ratings all have reinforced terminals
Alternate European ratings
Note:
UD or URD identifier may be replaced with ARGE, UB, URB, UC, URC, UE, URE, UF or URF. The B, C, D, E and F designate the speed characteristic and amount to assigning a new ampere rating. For example for a 500A UD and URD is the same construction as a 450A UE or URE and is the same as a 400A UF or URF.
Above are max ratings. For marketing reasons and customer requests, the voltage rating and the field in the catalogue number representing voltage rating may be less than the max shown.
Note: UD or URD identifier may be replaced with ARGE, UE, URD, UF or URF. The
D, E and F designate the speed characteristic and amount to assigning a new
ampere rating.
For example for a 500A UD and URD is the same construction as a
450A UE or URE and is the same as a 400A UF or URF.
Note: Above are max ratings. For marketing reasons and customer requests, the
voltage rating and the field in the catalogue number representing voltage rating
may be less that the max shown.
Alternate European ratings:
Note: UD or URD identifier may be replaced with ARGE, UE, URD, UF or
URF. The D, E and F designate the speed characteristic and amount to assigning a
new ampere rating.
For example for a 500A UD and URD is the same construction as
a 450A UE or URE and is the same as a 400A UF or URF.
Note: Above are max ratings. For marketing reasons and customer requests, the
voltage rating and the field in the catalogue number representing voltage rating
may be less that the max shown.
/ey